| System Performance Criteria | ||||||
| System Type | Static Loads | Rolling Loads | ||||
| Panel | Panel Size | Concentrated Load | Safety Factor (min.2.0) | Ultimated load | 10 Passes | 10,000 Passes |
| FS700 | 600x600x35mm 610x610x35mm | 318kg /700lbs | Pass | 636kg /1400lbs | 275kg 600lbs | 181kg 400lbs |
| FS800 | 600x600x35mm 610x610x35mm | 368kg/800lbs | Pass | 736kg/1600lbs | 318kg 700lbs | 275kg 600lbs |
| FS1000 | 600x600x35mm 610x610x35mm | 454kg/1000lbs | Pass | 909kg/2000lbs | 368kg 800lbs | 318kg 700lbs |
| FS1250 | 600x600x35mm 610x610x35mm | 568kg/1250lbs | Pass | 1136kg/2500lbs | 454kg 1000lbs | 368kg 800lbs |
| FS1500 | 600x600x35mm 610x610x35mm | 681kg/1500lbs | Pass | 1363kg/3000lbs | 568kg 1250lbs | 454kg 1000lbs |
| FS2000 | 600x600x35mm 610x610x35mm | 909kg/2000lbs | Pass | 1818kg/4000lbs | 681kg 1500lbs | 568kg 1250lbs |
| FS2500 | 600x600x35mm 610x610x35mm | 1136kg/2500lbs | Pass | 2272kg/5000lbs | 909kg 2000lbs | 681kg 1500lbs |
| FS3000 | 600x600x35mm 610x610x35mm | 1363kg/3000lbs | Pass | 2726kg/6000lbs | 1136kg 2500lbs | 909kg 2000lbs |
OA600 steel raised access flooring delivers multiple performance advantages, making it ideal for commercial buildings, data centers, and technical environments. Key benefits include:
High strength and long-lasting durability thanks to steel panel construction
Fire resistance for enhanced safety and compliance
Good acoustic performance to reduce noise transmission
Excellent thermal conductivity to support HVAC efficiency
Easy installation and maintenance, saving time and costs
Flexible layout adaptability, allowing quick reconfiguration for changing office or equipment requirements
This combination of strength, safety, and flexibility makes OA600 a reliable choice for modern raised floor applications.
Yes, OA600 steel raised access flooring can be fully customized to meet specific project requirements. Options include custom panel sizes, surface finishes, and accessories such as ramps, steps, and handrails. This flexibility allows the system to adapt to unique building layouts, specialized applications, and regional project needs, ensuring both functional performance and aesthetic integration.
The installation process for OA600 steel raised access flooring includes several key steps:
Preparation of the subfloor to ensure a level and stable base
Installation of the adjustable pedestal system for proper height and support
Placement of the steel panels, interlocking them securely
Cutting panels to fit around obstacles or structural features
Installation of required accessories, such as ramps, steps, or handrails
Final inspection and testing to verify compliance with applicable standards and regulations
This structured process ensures a safe, durable, and precise installation, suitable for commercial offices, data centers, control rooms, and other technical facilities.