ANTI-STATIC STEEL HPL RAISED ACCESS FLOORING

Anti-Static Steel HPL Raised Floor system boasts excellent anti-static performance, effectively eliminating static electricity produced by computers during operation and ensuring computer stability. This versatile flooring system finds wide application in the microelectronics industry, for the assembly of electronic components, semiconductors, electronic products, and large-scale and ultra-large-scale integrated circuits. Its use helps control electrostatic discharge and prevent damage to computer communication, various electronic devices, and static-sensitive devices, thereby avoiding damage to computer memory and electronic instruments. This system is also ideal for use in areas with anti-static requirements, such as static-sensitive munitions, flammable and explosive places, petrochemical workshops, hospital operating rooms, anesthesia rooms, and other similar places.These panels are non-combustible and adhere to Dawn standards as tested by CISCA.

FINISH OPTIONS

Tile factory laminated

  1.2mm HPL
      Pattern     45° Routed HPL     C-Trim Edge Trim     integral trim
  1.5mm HPL
      Pattern     45° Routed HPL     C-Trim Edge Trim     integral trim
  3.0mm HPL
      Pattern      45° Routed HPL     C-Trim Edge Trim     integral trim
      For additional laminate options,  Contact our sales team.

SYSTEM PERFORMANCE CRITERIA

System performance criteria are the most important to consider because they represent the performance in a typical installation. Panel only criteria such as concentrated load is often used to specify floor systems however, the test is not representative of an actual installation because it is performed with the panel testing blocks, not actual understructure.
  System Performance Criteria
System Type Static Loads Rolling Loads
   Panel Panel Size Concentrated
Load
Safety Factor
(min.2.0)
Ultimated load 10 Passes 10,000 Passes
   FS800 600x600x35mm
610x610x35mm
368kg/800lbs Pass 736kg/1600lbs 318kg
700lbs
275kg
600lbs
   FS1000 600x600x35mm
610x610x35mm
 454kg/1000lbs Pass 909kg/2000lbs 368kg
800lbs
318kg
700lbs
   FS1250 600x600x35mm
610x610x35mm
568kg/1250lbs Pass 1136kg/2500lbs 454kg
1000lbs
368kg
800lbs
   FS1500 600x600x35mm
610x610x35mm
681kg/1500lbs Pass 1363kg/3000lbs 568kg
1250lbs
454kg
1000lbs
   FS2000 600x600x35mm
610x610x35mm
909kg/2000lbs Pass 1818kg/4000lbs 681kg
1500lbs
568kg
1250lbs
   FS2500 600x600x35mm
610x610x35mm
1136kg/2500lbs Pass 2272kg/5000lbs 909kg
2000lbs
681kg
1500lbs
   FS3000 600x600x35mm
610x610x35mm
1363kg/3000lbs Pass 2726kg/6000lbs 1136kg
2500lbs
909kg
2000lbs
*A tests are performed using CISCA's Recommend Test Procedures for Access Floors with the exception of Design Load
1. Design load is tested using CISCA Concentrated Load test method on actual understructure instead of steel blocks. Design load is determined by taking the lesser value of ultimate load divided by two or the point at which permanent damage begins to occur (yield point).
2. Safety factor is the multiple of Design load to the Ultimate Load. International standards and Dawn Modular Floor recommend' a minium of 2.

UNDERSTRUCTURE OPTIONS

INSTALLATION

The finished access floor wil be rigid, free from vibration and rocking panels within a 3mm level over the entire space. Panels will be accurately cut to fit around all permanent features. All whole panels will be completely interchangeable allowing for any future changes. The access foor will maintain these origina conditions when sufficient panels have been removed for normal underfloor access.

ADVANTAGES

Electrostatic Discharge Protection: Anti-static raised access flooring prevents the buildup of static electricity, which can damage sensitive electronic equipment in data centers. This helps to protect the data center's equipment from electrostatic discharge (ESD).
Cable Management: Raised access flooring provides ample space for cable management, helping to keep cables organized and easily accessible for maintenance and upgrades.
Customizable Design: Anti-static raised access flooring is available in a range of finishes and colors, allowing for customizable design options that can complement the aesthetics of the data center.
Durability: Anti-static raised access flooring is made from high-quality materials, providing excellent durability and long-term performance.
Easy Installation: Raised access flooring is easy to install and can be customized to fit the unique needs of the data center.
Fire Resistance: Anti-static raised access flooring is often made from fire-resistant materials, providing an additional layer of safety and protection for the data center.
Sound Absorption: Raised access flooring can help to reduce noise levels in the data center, creating a quieter and more comfortable working environment for technicians and other staff.

NEED TO TALK? WE'RE HERE FOR YOU.

There's a lot to consider when it comes to ordering access floor. Let us know what you're looking for, and we'll help you determine which access floor options are best for your needs.

WE ARE WORKING WITH

RELATED PRODUCTS

FAQ

Solution

Quick Links

Contact Information
    info@dawnfloors.com
   +86-13861250682
    No.4 Wuqing Road, Henglin Town, Wujin District, Changzhou City, Jiangsu Province, China
© COPYRIGHT 2023 DAWN MODULAR FLOOR ALL RIGHTS RESERVED.